PRODUCTS - POWER CABLES
N2XH IEC 60502 - 0,6 / 1kV
* APPLICATION PLACE

Industrial establishments, hospitals, business centers, hotels, residences, under or on the plaster, humid (damp) or dry indorr / outdoor places.

* TECHNICAL DATA

Maximum working temperature : 90°C
Short circuit temperature : 250°C (Max for 5 Sec.)
Rated Voltage : Uo/U - 0,6 / 1 kV
Test Voltage : 3,5 kV (AC)
Blending Radius : 12 x D
Smoke Emission : EN61034-2
Acid Gas Emission : EN50267-2-1
Flame Propagation : EN60332-1-2



 

Size and weights

 

 

 

Electrical Specification

Nominal Cross Section

 

Overall diameter approx

Net weight approx

Standart delivery lenght

 Conductor DC resistance at 20°C max.

 

Current Carrying capacity

 

 

 

 

 

In ground 30°C max.

mm²

mm

kg/km

m

ohm/km

A

2x1.5

12

180

1000

12.1

20

2x2.5

12.5

220

1000

7.41

27

2x4

13.5

265

1000

4.61

37

2x6

15

340

1000

3.08

48

2x10

16.5

465

1000

1.83

66

3x1.5

12

200

1000

12.1

18.5

3x2.5

13

250

1000

7.41

25

3x4

14

310

1000

4.61

34

3x6

15.5

403

1000

3.08

43

3x10

17.5

565

1000

1.83

60

4x1.5

13

230

1000

12.1

18.5

4x2.5

14

290

1000

7.41

25

4x4

15

365

1000

4.61

34

4x6

16.5

485

1000

3.08

43

4x10

19

695

1000

1.83

60

4x16

21

980

1000

1.15

80

4x25

25.5

1470

1000

0.727

106

4x35

28

1910

1000

0.524

131

4x50

29.5

2220

1000

0.387

159

4x70

33.5

3085

1000

0.268

202

4x95

37

4150

1000

0.193

244

4x120

41

5140

500

0.153

282

4x150

46

6310

500

0.124

324

4x185

50.5

7890

500

0.0991

371

4x240

57.5

10140

250

0.0754

436