PRODUCTS - BUILDING WIRES
H05V-R IEC 227 HD 21.3 S3 / H07V-R IEC 227 HD 21.3 S3
* APPLICATION PLACE

This type is used in dry indoor places as fixed construction cable,on the plaster and under the plaster as in pipe, in the connection and distribution construction.

* TECHNICAL DATA

Maximum working temperature : 70°C
Short circuit temperature : 160°C (Max for 5 Sec.)
Rated Voltage : Uo/U - 300/500V (H05V) Uo/U - 450/750V (H07V)
Test Voltage : 2 kV - 2.5 kV (AC)



Size and weights

 

 

 

 

Electrical Specification

Type

Nominal Cross Section

Overall diameter approx

 

Net weight approx

Standart deliv- ery lenght

 

 Conductor DC resistance at 20°C max.

Current Carrying capacity 

 

 

 

 

 

 

 In ground 20°C max.

 in air 30°C max.

 

mm² 

 mm

kg/km

 m

 ohm/km

 A

A

 H07V-R

1.5

3

 20

100

12.10

15

24

 H07V-R

2.5

3.6

30

100

7.41

20

32

 H07V-R

4

4.1

50

100

4.61

25

42

 H07V-R

6

4.7

65

100

3.08

33

54

 H07V-R

10

5.8

110

100

1.83

45

73

 H07V-R

16

7.3

175

100

1.15

61

98

 H07V-R

25

9.0

270

100

0.727

83

129

 H07V-R

35

10.0

370

100

0.524

103

158

 H07V-R

50

12.0

480

1000

0.387

132

198

 H07V-R

70

13.0

690

1000

0.268

165

245

 H07V-R

95

15.0

940

1000

0.193

197

292

 H07V-R

120

16.5

1170

1000

0.153

235

344

 H07V-R

150

18.5

1440

1000

0.124

-

391

 H07V-R

185

20.0

1780

1000

0.0991

-

448

 H07V-R

240

23.0

2360

1000

0.0754

-

528

 H07V-R

300

26.0

2930

1000

0.0601

-

608

 H07V-R

400

29.0

3730

1000

0.0470

-

726

Phone : +251 11 1569926