PRODUCTS - BUILDING WIRES
H05Z1-U IEC 227 HD 21.3 S3  / H07Z1-U IEC 227 HD 21.3 S3
* APPLICATION PLACE

This type is used in dry indoor places as fixed construction cable,on the plaster and under the plaster as in pipe, in the connection and distribution construction, and having low emission of smoke and corrosive gases when affected by fire.

* TECHNICAL DATA

Maximum working temperature : 70°C
Short circuit temperature : 160°C (Max for 5 Sec.)
Rated Voltage : Uo/U - 300/500V (H05Z1) Uo/U - 450/750V (H07Z1)
Test Voltage : 2 kV - 2.5 kV (AC)
Smoke Emission : EN 61034-2
Acid Gas Emiision : EN 50267-2-1
Flame Propagation : EN 60332-1-2



Size and weights

 

 

 

 

Electrical Specification

Type

Nominal Cross Section

Overall diameter approx

 

Net weight approx

Standart deliv- ery lenght

 

 Conductor DC resistance at 20°C max.

Current Carrying capacity 

 

 

 

 

 

 

 In ground 20°C max.

 in air 30°C max.

 

mm² 

mm

kg/km

m

ohm/km

A

A

 H05V-K

0.50

2

 9

100

36

-

12

H05V-K

0.75

2.20

12

100

24,5

-

15

H05V-K

1

2.30

14

100

18,1

12

19

H07V-K

1.5

2.7

20

100

12.10

15

24

H07V-K

2.5

3.3

30

100

7.41

20

32

 H07V-K

4

4.0

50

100

4.61

25

42

 H07V-U

 6

4.5

 65

 100

3.08

33

54

 H07V-U

 10

5.5

 106

100

1.83

48

78